Stoebich Model P vs Smoke Guard 2500

The main difference is that the Stoebich Model P is a custom-made, high-temperature-rated, self-closing smoke curtain for very large openings (up to 32.8' x 24.9' certified), while the Smoke Guard 2500 (M2500) is a pre-engineered, UL 10D-rated fire and smoke system for openings up to 40' x 20'.

The Stoebich Model P uses a "Gravigen" drive that closes without external energy, and can be customized for high-temperature loads.

The Smoke Guard 2500 has a specific fire endurance rating and standard features for smoke and draft control systems. 

Cut_sheet_Stoebich_P_vs._Smoke_Guard_Model_2500_Fire-Smoke_1.png

Cut_sheet_Stoebich_P_vs._Smoke_Guard_Model_2500_Fire-Smoke_2.png

Cut_sheet_Stoebich_P_vs._Smoke_Guard_Model_2500_Fire-Smoke_3.png

Stoebich Model P Customization: Designed for highly custom solutions, offering made-to-measure widths and lengths, and can be designed to achieve high time classes at temperature loads up to \(1,112^{\circ }F\) (\(600^{\circ }C\)) or even higher.

Drive System: Features a "Gravigen" drive system that closes the curtain automatically without external energy when a fire alarm sounds.

Dimensions: Can be made in widths up to 32.8 feet (10 meters) and lengths up to 24.9 feet (7.6 meters) in its certified version, with larger dimensions being technically possible.

Flexibility: Suitable for various applications, including as a floor-closing, space-creating, or passable smoke curtain.

Smoke Guard 2500 Standardization: A code-compliant, pre-engineered system designed for large openings where both fire and smoke protection are required.

Ratings: Specifically UL 10D fire endurance rated and compliant with NFPA 105 smoke and draft control standards.

Dimensions: Certified for openings up to 40 feet wide by 20 feet tall.

Power: Requires a 120V AC power source and includes a 24V DC battery backup system.

Installation: Typically requires a factory-recognized installation by trained personnel.